Skip to Content
ID
7-508-1076
Name
Generators
Status
Interim Guidance
Updated
11/18/2019 2:55:45 PM
Released
05/26/2005
Description
 
Resource Category
Public Works
Primary Core Capability
Infrastructure Systems
Secondary Core Capability
Mass Care Services
Resource Kind
Equipment
Overall Function
 
Composition and Ordering Specifications
 
Supporting Core Capabilities
None
Components
Component Notes  
Kilowatts (kW) per EquipmentNot Specified
Component Types
Type Attribute
Type 12000 kW Generator Sound attenuated Trailer mounted (semi tractor) Up to 3015 Amps@ 480 Volts, 3 Phase, 60 Hz Dry weight 89,000 lbs
Type 21500 kW Generator Sound attenuated Trailer mounted (semi tractor) Up to 2260 Amps@ 480 Volts, 3 Phase, 60 Hz Dry weight 59,000 lbs
Type 3600 kW Generator; Sound attenuated Trailer mounted (semi tractor) Up to 2080 Amps@ 208 Volts, 3 Phase, 60 Hz / up to 902 Amps@ 480 Volts 3 Phase, 60 Hz Dry weight 37,000 lbs
Type 4400 kW Generator Sound attenuated Trailer mounted (pull behind) Multi-voltage distribution panel Up to 1390 Amps @ 208 Volts, 3 Phase, 60 Hz/up to 602 Amps@ 408 Volts 3 Phase, 60 Hz Dry weight 16,800 lbs
Type 5125 kW Generator Sound attenuated Trailer mounted (pull behind) Multi-voltage distribution panel Up to 433 Amps@ 208 Volts, 3 Phase, 60 Hz / up to 188 Amps @ 480 Volts 3 Phase, 60 Hz Dry weight 10,610 lbs
Fuel Tank Capacity Per EquipmentNot Specified
Component Types
Type Attribute
Type 11250 Gallons
Type 21250 Gallons
Type 3660 Gallons
Type 4470 Gallons
Type 5223 Gallons
Equipment DimensionsNot Specified
Component Types
Type Attribute
Type 140' Long x 8' Wide x 13' .5" Tall
Type 240' Long x 8' Wide x 13' .5" Tall
Type 340' Long x 8' Wide x 13' .5" Tall
Type 423' Long x 8' Wide x 13' .5" Tall
Type 518' .5" Long x 6' .5" Wide x 9' Tall
Potential application example Per EquipmentNot Specified
Component Types
Type Attribute
Type 1Single or multiple units for: Power plants, heavy industrial facility, high-rise buildings
Type 2Single or multiple units for: Universities, hospitals, medium to large manufacturing facility
Type 3Retail store, HVAC system power, multi-story/buildings, light manufacturing, apartment buildings
Type 4Large office building, public schools, libraries, and communication equipment
Type 5Small office building, emergency mobile trailers & operations, restaurants
Setup time Per EquipmentNot Specified
Component Types
Type Attribute
Type 1Cables from generator to main power feed estimated at 5+ hours
Type 2Cables from generator to main power feed estimated at 5+ hours
Type 3Cables from generator to main power feed estimated at 3+ hours
Type 4Cables from generator to main power feed estimated at 2+ hours
Type 5Cables from generator to main power feed estimated at 1 hour
Equipment ExampleNot Specified
Component Types
Type Attribute
Type 1XQ2000
Type 2XQ1500
Type 3XQ600
Type 4XQ400
Type 5XQ125
689
Notes
References
Reference